1800 425 6594

PRODUCT DETAILS

Sinwave Inverter

Nova series Inverter is desirable long backup power solution for home and office appliances. It is not only an inverter but also contains a powerful intelligent charger. It provides pure sine wave power to all kinds of loads.

 



MODEL

Nova500 VA

800 VA

1000 VA

1000 VA

2000 VA

3000 VA

DC INPUT

Nominal input voltage

12 V

24/48 V

DC input voltage range

10 V ~ 15 V

20 V ~ 30 V/40V-60V

AC INPUT

Bypass voltage

0 ~ 264 Vac for 220 Vac / 230 Vac / 240 Vac,
0 ~ 132 Vac for 100 Vac / 110 Vac / 115 Vac / 120 Vac

AC voltage

150 ~ 282 Vac for 220 Vac, 156 ~ 294 Vac for 230 Vac,163 ~ 307 Vac for 240 Vac,
68 ~ 128 Vac for 100 Vac, 75 ~ 141 Vac for 110 Vac, 79 ~ 148 Vac for 115 Vac, 82 ~ 154 Vac for 120 Vac.

Frequency

50 Hz / 60 Hz (auto-sense & settable: 5% ~ 15%, default 15%),
42.5 ~ 57.5 Hz for 50 Hz, 51 ~ 69 Hz for 60 Hz

Input voltage of generator

99 ~ 282 Vac for 220 Vac, 104 ~ 294 Vac for 230 Vac, 108 ~ 307 Vac for 240 Vac,
45 ~ 128 Vac for 100 Vac, 50 ~ 141 Vac for 110 Vac, 52 ~ 148 Vac for 115 Vac, 54 ~ 154 Vac for 120 Vac.

Input frequency of generator

40 ~ 70 Hz

Input power limitation

Rated power 10% ~ 150%,regulating step 10%, default 120%

OUTPUT

DC mode output voltage

220 Vac / 230 Vac / 240 Vac ± 5% or 100 Vac / 110 Vac / 115Vac / 120 Vac ± 5% (settable)

AC mode output voltage

174 ~ 242Vac for 220Vac, 182 ~ 253Vac for 230Vac, 190 ~ 264Vac for 240Vac,
79 ~ 109Vac for 100Vac, 87 ~ 121Vac for 110Vac, 93 ~ 125Vac for 115Vac, 95 ~ 133Vac for 120Vac.

Nominal output frequency

50 Hz / 60 Hz ± 0.3 (auto-sense & settable)

Output waveform

Pure sine wave

Output power

400 W

480 W

800 W

800 W

1600 W

2400 W

Efficiency

Max. 95% (mains mode); Max. 80% (inverter mode)

ECO mode

Settable, load < 3%, enter in 80 s

No-load shutdown

Settable, time can be set (1 ~ 99 min), load can be set (3% ~ 50%)

Transfer time

≤ 10 ms

≤ 15 ms

Power factor

1.0

THDV

< 5% (linear load)

Inductive load

Yes

Motor load

Yes

Rectifier load

Yes

Overload

Mains mode: 110% for 120 s, 125% for 60 s, 150% for 10 s (switch to bypass)
Inverter mode: 110% for 60 s; 125% for 10 s; 150% for 10 s (shut down)

BATTERIES

Charging current (selectable)

Default 10 A

Default 20 A, regulating step 1 A (< 10 A) / 5 A (> 10 A)

Max. 15 A

Max. 20 A

Max. 40 A

Max. 40 A

Max. 40 A

Max. 40 A

Equalizing charge voltage

Single battery 14.4Vdc (default), 13.6 ~ 15Vdc adjustable

Floating charge voltage

Single battery 13.7Vdc (default), 13.2 ~ 14.6Vdc adjustable

Charge mode

3 stage charge mode

DOD

Single battery 10.8 Vdc (default), 9.6 ~ 13 Vdc settable

EOD

Single battery 10.2 Vdc (default), 9.6 ~ 11.5 Vdc adjustable

Reverse warning

Buzzer