TRUE ONLINE LF Model

IGA True online series UPS provides reliable protection for all high end and rugged load condition and equipped to manage all power disturbances. IGATECH Online UPS is an exceptional and innovative electrical apparatus that provides emergency power to a load when the input power source, or the main fails and also give protection to the attached equipment against power fluctuations, spikes, surges, frequency variations and line noise etc. Therefore, our advanced technology Online UPS system plays an essential role in proper functioning of any type of organization without interruption of power.

Request a Quote

Description

TRUE ONLINE LF Model 1:1 AND 3:1

FEATURES

  •  Built in isolation Transformer.
  • Wide input voltage range minimizing battery wastage and enhancing battery utilization and life.
  • Double conversion online.
  • Micro controller based reliable design using IGBT.
  • In built Manual & static (option) bypass facility.
  • Heavy duty charger for long backup.
  • Multiple protection features to ensure load safety.
  • DC- Start Function
  • EMI, RFI, Surge & Short circuit protection.
  • Rating ranges

1KVA – 10KVA —– 1PH In: 1PH Out

3KVA – 30KVA —– 3PH In: 1PH Out

  • Pure sine wave output with <2% THD for linear and <5% for non linear load.
  • Intelligent overload protection.
  • Rs 232/SNMP(optional)

MODEL IGOL2K IGOL3K IGOL5K IGOL7.5K IGOL10K IGOL15K IGOL20K IGOL25K IGOL40K
Capacity
2000VA
3000VA
5000VA
7500VA
10000VA
15000VA
20000VA
25000VA
40000VA
DC Voltage
72-96VDC
120-240VDC
144-360VDC
240-360VDC
360-384VDC
Input Voltage
160-270 VAC (1 Phase)
160-270VAC(1ph)/300-470VAC(3ph)
300-470 VAC (3 Phase)
Input power factor
>0.95
>0.99
Output Voltage
220/230/240 VAC +/-1%
Load Power factor
0.8 (0.9 Optional)
Over Load
125% 10 mnts, 150% 1 mnts
O/P Wave form,THD
Pure Sine wave <2% Linear load <5% for Non linear Load
O/P Frequency
50 Hz +/-0.05 Hz (Free running), 46 Hz-54 Hz Synchronised mode
Inverter Efficiency
90%
91%
90%
91%
91%
Technology
Advanced DSP Design
Crest factor
3:1 (Max)
Communication
RS 232/SNMP
Noice at 1M
<62 dB
<68 dB
Cooling
Forced Air cooling
Protections
Over load, Short circuit, Batt. Low, Output Under/Over, Input under / over
Change Over
No Break Change over
Galvanic Isolation
Inverter Isolation Transformer
Display
Input volt, Output volt, Battery volt & current, Load current, Frequency, System status, Trip Conditions
LED Indications
Mains on, Charger on, Static on, Inv On, Battery mode, Battery low, Over load
Working temperature
0-55 degree Ambient temp
Humidity
95 degree non condensing
Safety standard
Complies IEC-62040-1, IS 16242
Dimension in mm L X W X H
620 X 210 X 625
620 X 210 X 625
620 X 210 X 625
650 X 260 X 625
700 X 460 X 790
700 X 460 X 790
750 X 470 X 995
750 X 470 X 995
750 X 470 X 995
Weight
40KG
48KG
55KG
70KG
130KG
150KG
175KG
200KG
250KG